451 D STREET is located in Boston’s vibrant Innovation/Seaport District and offers numerous amenities including on-site parking, conference center and a fitness center, plus shuttle service to North and South Stations. The property recently underwent a lobby renovation and the addition of a tenant amenity center.
Building Highlights
On-Site Parking
536 parking spaces
(40 underneath building).
Conference Center
On-site conferencing center.
Amenity Center
Brand-new tenant amenity center featuring a lounge area, kitchen, games and conference center.
On-site Cafe
Refreshed on-site cafe offering breakfast and lunch.
Bicycle Storage
Enclosed bike storage.
Fitness Center
3,000 SF on-site fitness center with towel service.
11'4"– 12'3" Clear Heights
Building Base Description
Property Specifications
Building Size
477,132 SF
Floor
Nine Floors
Clear Height
11'4"–12'3"
Year Built/Renovated
1910/2016
Floor Load
150 lbs/SF West Side 300 lbs/SF East Side
Column Spacing
14'6" West Side
18' East Side
Elevators
Six passenger elevator and one 4,000-lb freight (replacement 2018/20)
Loading Dock
One shared truck-height central loading dock
Fire Protection
Automatic wet sprinklered building to accomodate predominantly light hazard occupancy spaces
Wired Certification
Platinum Wired Certification
Fact Sheet
Electrical
Primary Feed to Building
13.8 kV service entrance feeds six 4000A, 480V, 3Ph main switchboards
Tenant Standby Power
Central Lab standby gas-fired generator to provide 5 Watts/SF for the Lab spaces
Communications
Multiple service entrances located at the basement level. Verizon, Verizon Business, Light Tower, AT&T and Cogent. Provisions for the future service entrance at the E Street side of the building exist as well
Emergency Power
275 kW diesel life safety generator that serves common area lighting, fire alarm, elevator and fire pump. Tenant spaces utilize battery systems for their emergency lighting requirements
HVAC
Lab
Central lab exhaust and makeup air systems to accommodate 1.5 cfm/SF of lab space
Office
Two 500-ton cooling towers and one 330-ton cooling tower serve three condenser water riser systems. Tenant provides water source heat pump units for space heating and cooling
Heating Plant
Three 1.7 million Btu gas-fired boilers supplement the condenser water loop